Orifice (MA)
Libraries:
Simscape /
Fluids /
Moist Air /
Valves & Orifices
Description
The Orifice (MA) block models pressure loss due to a constant or variable area orifice in a moist air network. The block calculates fluid properties inside the valve from inlet conditions. There is no heat exchange between the fluid and the environment, and therefore phase change inside the orifice only occurs due to a pressure drop or a propagated phase change from another part of the model.
The orifice can be constant or variable. When the Orifice type
parameter is Variable, the physical signal at port
S sets the position of the control member, which opens and
closes the orifice.
Orifice Parameterizations
The block behavior depends on the Orifice parametrization parameter:
Cv flow coefficient— The flow coefficient Cv determines the block parameterization. The flow coefficient measures the ease with which the moist air can flow when driven by a certain pressure differential.Kv flow coefficient— The flow coefficient Kv, where , determines the block parameterization. The flow coefficient measures the ease with which the moist air can flow when driven by a certain pressure differential.Sonic conductance— The sonic conductance of the resistive element at steady state determines the block parameterization. The sonic conductance measures the ease with which the moist air can flow when choked, which is a condition in which the flow velocity is at the local speed of sound. Choking occurs when the ratio between downstream and upstream pressures reaches a critical value known as the critical pressure ratio.Orifice area— The size of the flow restriction determines the block parametrization.
Variable Orifice
When you set Orifice type to
Variable and Opening
characteristic to Linear, the block
uses the input at port S to calculate the
orifice opening,
where S is the value of the signal at port S, and Smin and ΔS are the values of the Control member position at closed orifice and Control member travel between closed and open orifice parameters, respectively.
When you set Orifice type to
Variable and Opening
characteristic to Tabulated, the block
interpolates the orifice characteristics from the Control member
position vector parameter and the input at port S.
For a variable orifice, the flow rate in the orifice depends on the Opening characteristic parameter:
Linear— The measure of flow capacity is proportional to the control signal at port S. As the control signal increases, the measure of flow capacity scales from the specified minimum to the specified maximum.When you set Orifice parameterization to
Cv flow coefficientorKv flow coefficient, the block treats the parameter xT pressure differential ratio factor at choked flow as a constant independent of the control signal.Tabulated— The block calculates the measure of flow capacity as a function of the control signal at port S. This function uses a one-dimensional lookup table.When you set Orifice parameterization to
Cv flow coefficientorKv flow coefficient, the block treats the parameter xT pressure differential ratio factor at choked flow as a function of the control signal.
Momentum Balance
The block equations depend on the Orifice parametrization parameter.
When you set Orifice parametrization to Cv
flow coefficient, the mass flow rate is
where:
Cv is the flow coefficient.
N6 is a constant equal to 27.3 when mass flow rate is in kg/hr, pressure is in bar, and density is in kg/m3.
Y is the expansion factor.
pin is the inlet pressure.
pout is the outlet pressure.
vin is the inlet specific volume.
The expansion factor is
where:
Fγ is the ratio of the isentropic exponent to 1.4.
xT is the value of the xT pressure differential ratio factor at choked flow parameter.
The block smoothly transitions to a linearized form of the equation when the pressure ratio, , rises above the value of the Laminar flow pressure ratio parameter, Blam,
where:
When the pressure ratio, , falls below , the orifice becomes choked and the block uses the equation
When you set Orifice parametrization to Kv
flow coefficient, the block uses the same equations as the
Cv flow coefficient parametrization, but replaces
Cv with
Kv using the relation .
When you set Orifice parametrization to Sonic
conductance, the mass flow rate is
where:
C is the sonic conductance.
Bcrit is the critical pressure ratio.
m is the value of the Subsonic index parameter.
Tref is the value of the ISO reference temperature parameter.
ρref is the value of the ISO reference density parameter.
Tin is the inlet temperature.
The block smoothly transitions to a linearized form of the equation when the pressure ratio, , rises above the value of the Laminar flow pressure ratio parameter Blam,
When the pressure ratio, , falls below the critical pressure ratio, Bcrit, the orifice becomes choked and the block switches to the equation
The Sonic conductance setting of the
Orifice parameterization parameter is for pneumatic
applications. If you use this setting for moist air with high levels of trace
gasses or are modeling a fluid other than air, you may need to scale the sonic
conductance by the square root of the mixture specific gravity.
When you set Orifice parametrization to
Orifice area, the mass flow rate is
where:
Cd is the value of the Discharge coefficient parameter.
γ is the isentropic exponent.
The block smoothly transitions to a linearized form of the equation when the pressure ratio, , rises above the value of the Laminar flow pressure ratio parameter, Blam,
When the pressure ratio, , falls below , the orifice becomes choked and the block uses the equation
Mass Balance
The block conserves mass through the valve
where ṁ is the mass flow rate and the subscript w denotes water vapor, the subscript g denotes trace gas, and the subscript d denotes water droplets.
Energy Balance
Energy is conserved in the orifice,
where:
ΦA is the energy flow at port A.
ΦB is the energy flow at port B.
Assumptions and Limitations
There is no heat exchange between the valve and the environment.
Ports
Conserving
Input
Parameters
References
[1] ISO 6358-3. "Pneumatic fluid power – Determination of flow-rate characteristics of components using compressible fluids – Part 3: Method for calculating steady-state flow rate characteristics of systems". 2014.
[2] IEC 60534-2-3. "Industrial-process control valves – Part 2-3: Flow capacity – Test procedures". 2015.
[3] ANSI/ISA-75.01.01. "Industrial-Process Control Valves – Part 2-1: Flow capacity – Sizing equations for fluid flow underinstalled conditions". 2012.
[4] P. Beater. Pneumatic Drives. Springer-Verlag Berlin Heidelberg. 2007.
Extended Capabilities
Version History
Introduced in R2025a