Grid Single Phase Source

Grid Single Phase Source with source impedance model using RL branch based on short circuit level or transformer capacity & impedance.

You are now following this Submission

Grid Single Phase Source with source impedance model using RL branch.
User can define the grid source line voltage, frequency, transformer power capacity, transformer impedance, short circuit level and X/R ratio to determine the source impedance, R and L.
Determine R & L based on transformer power capacity and transformer impedance
Zbase = Vrms^2/S;
Z = Zbase * (ZTx/100);
R = Z/sqrt(1+X_R^2);
L = (R*X_R)/(2*pi*f0);
Determine R & L based on 3 phase short circuit level at base voltage
XL = Vrms^2/SC;
R = XL/X_R;
L = XL/(2*pi*f0);
Developed by Rodney Tan (PhD)
Version 1.00 (Aug 2025)

Cite As

Rodney Tan (2026). Grid Single Phase Source (https://uk.mathworks.com/matlabcentral/fileexchange/181856-grid-single-phase-source), MATLAB Central File Exchange. Retrieved .

General Information

MATLAB Release Compatibility

  • Compatible with any release

Platform Compatibility

  • Windows
  • macOS
  • Linux
Version Published Release Notes Action
1.0.0