Three-Phase Fault
Implement programmable phase-to-phase and phase-to-ground fault breaker system
Libraries:
Simscape /
Electrical /
Specialized Power Systems /
Power Grid Elements
Description
The Three-Phase Fault block implements a three-phase circuit breaker where the opening and closing times can be controlled either from an external Simulink® signal (external control mode), or from an internal control timer (internal control mode).
The Three-Phase Fault block uses three Breaker blocks that can be individually switched on and off to program phase-to-phase faults, phase-to-ground faults, or a combination of phase-to-phase and ground faults. The arc extinction process of the Three-Phase Fault block is the same as for the Breaker block. See the Breaker block for details on the modeling of the single-phase breakers.
The ground resistance Rg is automatically set to 106 ohms when the ground fault option is not programmed. For example, to program a fault between the phases A and B you need to select the Phase A and Phase B block parameters only. To program a fault between the phase A and the ground, you need to select the Phase A and Ground parameters and specify a small value for the ground resistance.
If the Three-Phase Fault block is set in external control mode, a control
input appears in the block icon. The control signal connected to the fourth Simulink input must be either 0
, which opens the breakers, or any
positive value, which closes the breakers. For clarity, a 1
signal is
commonly used to close the breakers. If the Three-Phase Fault block is set in
internal control mode, the switching times and status are specified in the dialog box of the
block.
Series Rs-Cs snubber circuits are included in the model. They can be optionally connected to the fault breakers. If the Three-Phase Fault block is in series with an inductive circuit, an open circuit or a current source, you must use the snubbers.
Examples
Ports
Input
Conserving
Parameters
Extended Capabilities
Version History
Introduced before R2006a