Modbus properties
Use the Modbus® properties to configure the mode of operation, client device settings, and server register settings.
You can set these parameters to configure the Modbus properties.
Communication Interface
Select the type of communication interface the blocks will use for Modbus serial communication.
Settings
Default:
RS485
Mode
Select the Modbus mode of operation for the model. This parameter also determines the
type of blocks that can be used in the model. For example, in the
Client
mode, you can use only the Modbus RS485
Client Read and the Modbus RS485 Client
Write blocks. Similarly, in the Server
mode,
you can use only the Modbus RS485 Server
Read and the Modbus RS485 Server
Write blocks.
Settings
Default:
Client
Server
Server ID
Enter the unique 8-bit Modbus server address or identifier.
Settings
Default:
1
Dependencies
To enable this parameter, set Mode to
Server
.
Configure Coils
Select this parameter to configure the starting address and the number of coil registers.
Settings
Default: Selected
Dependencies
To enable this parameter, set Mode to
Server
.
Coil Register Parameters
Parameter | Description | Default Value |
---|---|---|
Start address | Starting address of the coil register Dependencies: To enable this parameter, select Configure Coils. | 0 |
Quantity | Number of coil registers Dependencies: To enable this parameter, select Configure Coils. | 1 |
Configure Discrete Inputs
Select this parameter to configure the starting address and the number of discrete input registers.
Settings
Default: Selected
Dependencies
To enable this parameter, set Mode to
Server
.
Discrete Input Register Parameters
Parameter | Description | Default Value |
---|---|---|
Start address | Starting address of the discrete input register Dependencies: To enable this parameter, select Configure Discrete Inputs. | 0 |
Quantity | Number of discrete input registers Dependencies: To enable this parameter, select Configure Discrete Inputs. | 1 |
Configure Holding registers
Select this parameter to configure the starting address and the number of holding registers.
Settings
Default: Selected
Dependencies
To enable this parameter, set Mode to
Server
.
Holding Register Parameters
Parameter | Description | Default Value |
---|---|---|
Start address | Starting address of the holding register Dependencies: To enable this parameter, select Configure Holding registers. | 0 |
Quantity | Number of holding registers Dependencies: To enable this parameter, select Configure Holding registers. | 1 |
Configure Input registers
Select this parameter to configure the starting address and the number of input registers.
Settings
Default: Selected
Dependencies
To enable this parameter, set Mode to
Server
.
Input Register Parameters
Parameter | Description | Default Value |
---|---|---|
Start address | Starting address of the input register Dependencies: To enable this parameter, select Configure Input registers. | 0 |
Quantity | Number of input registers Dependencies: To enable this parameter, select Configure Input registers. | 1 |
Received timeout (ms)
Enter the maximum time in milliseconds to wait for a response from the Modbus server. If the MODBUS server does not acknowledge the client within the specified time, then the communication is no longer valid.
Settings
Default:
100
Dependencies
To enable this parameter, set Mode to
Client
.